chart 4.
figure 2-12
chart 1.
chart 3.
chart 2.
TM 11-5820-890-30-4
2-29. OPERATIONAL CHECK.
Before beginning operational check, install new holding battery to replace holding battery removed for shipment.
The operational check provides a step-by-step procedure for evaluating an RT. If the operational check is
passed, the RT can be returned to service. If it does not pass the test, the bad module or the troubleshooting
chart to be used will be identified. The troubleshooting procedures are in paragraph 2-30.
The operational check is divided into steps. Each step verifies a particular function. Follow the instruction in the
Action column. Check the response. If the response is correct, proceed with the next lettered step. When a
Step has been completed, proceed with the next Step. A no response in the Response column means that
any response is not of interest.
The switch settings for the test equipment are given in the EQUIPMENT PRESETS section of each step. Set the
test equipment switches to the indicated presets and then verify the settings.
If a test response is incorrect,
check the equipment settings and the test adapter cabling before going to a troubleshooting chart or replacing a
bad module.
WARNING
Connect the test setups only when directed, and with the power supply set to OFF. The large
current capacity of the test power supply can cause personal injury. Verify the test setup before
turning the power supply on.
Whenever either cover is removed, take all proper electrostatic discharge (ESD) precautions.
Static electricity can damage the RT modules.
2-28
